ATEX Explosion Protected Power Supply ASPS-2GD

atex-power-supply-asps-2gd
atex-power-supply-asps-2gd

Power supply and in-/out module for indicator INDATEX 2GD, protection according to ATEX II (2)2G, [Ex ib] / Ex d IIC T4 Gb and ATEX II (2)2D, [Ex ib] / Ex tb IIIC T140°C Db, application in ATEX hazardous area,  zones 1 & 21.

See further under the tab Product information.

  1. Type: ASPS-2GD Price: On application

ATEX Explosion Protected Power Supply ASPS-2GD

  • power supply for indicator INDATEX 2GD, with 4 Exi data inputs
  • transforms hazardous voltages from a safe environment to an intrinsic safety voltage
  • through the 4 intrinsically safe inputs and 4 intrinsically safe or 4 unprotected data outputs, the ASPS-2GD module allows to receive the signals from outside and to manage intrinsically safe devices or devices with greater absorption, such as relays, placed in the Exd box
  • designed in accordance ATEX94 / 9 / CE Directive and EN60079-0 / 60079-11 / 60079-31 standards
  • aluminum housing, protection class II 2 GD Ex d IIC Ex tD A21 IP66
  • versions for different voltages: 230Vac, 115Vac, 24Vac, 24Vdc
  • properties intrensical safe power output:
    – Vmax: 10.5 Vdc
    – Imax: 140 mA
    – Uo: 12.6 Vdc
    – Io: 340 mA
    – Lo 700 mH
    – Co: 6.8 uF
  • intrinsic safety:
    – Ui: 40 Vdc
    – Ii: 30 mA
    – Li 0 mH
    – Ci: 0 uF
  • Note: If these inputs and outputs are powered through an intrinsic safety voltage inside the PW200XRD, the overall max. absorbable current from the 4 outputs and 4 inputs is 40mA; so, if just 1 output is used, it can supply up to 20mA
    equipped with 1 m connection cable to the indicator
  • unprotected:
    – Umax: 48 Vac o 60Vdc
    – Imax: 150 mA

Schedule ATEX Power Supply ASPS-2GD with INDATEX-2GD indicator